| Power Supply |
AC 208 -240VAC, single phase, ( 50Hz or 60Hz can be selected in the options bar ).
|
| Max Power Input |
5.44 kW |
| Nominal Cooling Capacity |
9 kW, 30708 Btu/h, 7738 kcal/h |
| Compressor |
Rotary Compressor, 2.64 kW (50 Hz), 2.71 kW (60 Hz) |
| Refrigerant |
R410A |
| Temperature Control |
5~30 °C |
| Temperature Accuracy |
± 1 °C |
| Heating Exchanger |
Aluminum |
| Water Pump |
0.55 kW (50 Hz), 0.75 kW (60 Hz)
|
| Water Flow Rate (Head Pressure) |
75 Liter/minute ( 28 meters high, 40psi )
|
| Maximum Water Pressure |
62 psi (50 Hz), 75 psi (60 Hz)
|
|
Water Tank
|
- 40 L, distilled water only.
- The water chiller should not be connected to a system with a capacity more than the tank's capacity itself.
- Do not use deionized water as the cooling agent, DI water may cause the copper pipe to corrode, mainly pitting, and leak over time.
- Distilled water is required as the coolant.
|
|
Pipe Connection
|
- Φ12mm push-to-connect connector
- 8mm I.D, 12mm O.D. polyurethane tube is included
|
| Water Filter |
- One water filter is included for immediate use.
- Replace the water filter every 3 to 6 months based on water quality and usage. Please click the pictures below to learn more.

|
| Noise |
80dBA
|
| Protection |
Protected from over-temperature and Min 2 L/min water flow
|
Compliance
|
- CE approval
- NRTL or CSA is available upon request at extra cost, please contact our sales representatives for a quote.
|
| Warranty |
- One-year limited warranty with lifetime support
|
| Application Notes |
- Use of tap water is prohibited.
- Please connect the chiller water outlet to the equipment water inlet and the chiller water inlet to the equipment outlet. Otherwise, the water flow sensor on the equipment may fail to work due to the wrong water flow direction
|